"Effect of different façade systems on the cooling capacity of a cooled ceiling - Tracer gas measurement of the air flow";
Vortrag: 10th Nordic Symposium on Building Physics, Lund, Sweden; 15.06.2014 - 19.06.2014; in: "NSB 2014,10th Nordic Symposium on Building Physics", Grafisk gruppen AB, (2014), ISBN: 978-91-88722-53-9; Paper-Nr. 5, 8 S.



Kurzfassung englisch:
The aim of the work is to clarify how the façade system and the cooling ceiling impacts the air movement within a room. Therefore tracer gas measurements with different inject locations and different room set-ups were done. One part of the results show the impact of different façade systems - a single skin façade and a single
storey double skin façade - on the air movement. The measurements show an increase of concentration within the ceiling zone which is attributed to a higher air flow rate over the ceiling.
Furthermore different set ups of the cooling ceilings were measured - one with natural ventilation over the suspended cooling ceiling and one without natural ventilation. The measurement results
show that there is a decrease of concentration due to missing natural ventilation. The measurement results show a clear difference in the rate of concentration on different room points due to solar radiation, the location of impact and the room set up.

Schlagworte:
Air flow, tracer gas measurement, comfort, façade systems, cooling ceiling, cooling capacity